Introducing
Your new presentation assistant.
Refine, enhance, and tailor your content, source relevant images, and edit visuals quicker than ever before.
Trending searches
A few tips for compressed air design:
Compressors when design in laboratory applications will likely be of a higher quality than for workshop applications as laboratory applications will probably necessitate an oil free installation..
Also workshops will probably require a lower level of filtration but have a larger receiver as workshop loads, if used for power tools, will be quite “spiky” compared with a laboratory.
There may not be a requirement for driers or a different type of drier could work (work shop application)
The standards for different applications are defined in ISO 8573. Laboratories will general require class 1 air (possibly not with a -70C dewpoint). Workshops more likely to be a class 4 or 5 – you should agree this with your client
Medical air is produced at a nominal pressure of 4 bar (400kPa) and surgical air at 7-9 bar (700-900kPa). Typical receiver pressures vary between 9.5 and 12.5 bar.
A plant of the above type is used to supply a 700 kPa surgical air system. The requirements at the terminal unit now stand at 350 l/min at the front of the terminal unit i.e. delivered flow. Given pressure drops across terminal units and pendant hoses, a dynamic pressure of about 8 bar and a static pressure of about 9 bar are required at the rear of the terminal unit.
Given pipeline pressure drop allowances a plant output pressure of about 9.5 bar (dynamic) would be required to guarantee the terminal unit flow. Many installations use a pipeline pressure of 10-11 bar, with local pressure regulation (adjacent to theatres), adjusted during commissioning to give the required terminal unit performance. Such a system requires a typical receiver pressure of between 12 and 13 bar.
Unlike natural gas, propane is heavier than air (1.5 times as dense). In its raw state, propane sinks and pools at the floor. Liquid propane will flash to a vapour at atmospheric pressure and appears white due to moisture condensing from the air.
When properly combusted, propane produces about 50 MJ/kg. The gross heat of combustion of one normal cubic meter of propane is around 91mega joules
Propane combustion is much cleaner than gasoline combustion, though not as clean as natural gas combustion.
Natural gas (methane) is the most common fuel gas, but others include:
Uncompressed Hydrogen or compressed hydrogen may be used as a fuel gas
Coal gas or Town gas, In British usage, coal gas specifically means gas made by the destructive distillation of coal.
The term is not applied to other coal-derived gases, such as water gas, producer gas and syngas. United States usage may be different. Coal gas was introduced in the UK in the 1790s as an illuminating gas by the Scottish inventor William Murdoch and became very widely used for lighting, cooking, heating and powering gas engines.
Parameters
The image below is a schematic block flow diagram of a typical natural gas processing plant. It shows the various unit processes used to convert raw natural gas into sales gas pipelined to the end user markets.
The block flow diagram also shows how processing of the raw natural gas yields by product sulphur, by product ethane, and natural gas liquids (NGL) propane, butanes and natural gasoline
Below is a chart showing the main properties, hazards, precautions and uses of a range of medical gases:
This list is not exhaustive you must for your assignment carry out you own research?
Applicable regulations and legislation are as follows:
Design Guides & Standards
Applicable regulations and legislation
Applicable regulations and legislation are as follows:
http://www.igem.org.uk/technical-standards/standards.aspx
This list is not exhaustive you must for your assignment carry out you own research?
Throughout healthcare premises there is a need for a varied amount of medical gases. Below is a list of gases supplied via pipeline systems in the establishments:
The above drawing and picture demonstrates a compressed gas cylinder manifold system. These systems are used to supply oxygen, medical or air surgical, air nitrous oxide, oxygen/carbon dioxide mixture or entonox/equinox.
A typical vacuum system extracted from an Eastwood park training book.
Medical vacuum systems are designed to produce a vacuum of 300 mmHg (kPa) at flow rate of 40 litres per minute at the most remote terminal unit. In reality flow rates are commonly far lower than this, typically around 6 litres per minute.
LPG installations are covered by BS5482: parts 1,2&3
LPG is stored in tanks that range in size from domestic 1/2 tonne to commercial 113,5,7 and 12 tonne tanks
Another method of sizing tanks is to use their water capacity i.e. 450 litres
Also refer to Calor Gas brochure
(separate hand out)
Follow on Exercise:
A small office block has a 50kW gas boiler & a ‘six hob’ gas cooker. Determine the total flow rate & pipe size if the distribution pipe totals 30m from the meter & the pipe work losses should not exceed 1mbar
1mbar = 100 Pascal's = 0.01mh
Specific gravity of gas, S = 0.6 m/s2
for the assignment brief Assume 3 Gas Boilers & 3 Bunsen burners
For volume flows up to 160 m3/hr ( ~ 1750 kw /hr ) a diaphragm meter may used. However, this is a bulky meter and two to three times more expensive than an equivalent rotary meter. If the turndown ratio is not critical, especially if there is a space limitation, a rotary meter may be used. Example :- a gas supply a workshop with four 60 kw radiant heaters each controlled with an on / off thermostat then a rotary meter would be applicable.
The pressure drop across s the meter is also important, A 100mm pipe may be able to supply two boilers rated at 750 kw input, however the pressure drop across a 100mm meter located in the basement was sufficient to breach the Gas Safety Regulation for the boilers located five storeys above on the roof. Instead the 100mm was removed and an 80mm meter was installed adjacent to each boiler.
An alternative for very low gas flows is a Rotary Piston meter (such as the Delta QD). They have been especially designed for industrial use and for secondary measurement and are particularly adapted when the flow can be low or irregular. ( Model QD25 1 to 25 m3 / hr and the QD60 2.5 to 60 m3 / hr )
Extract from Institute for Plumbing
The selection of the correct type of gas meter and ancillary equipment is important otherwise some of the gas usage may not be monitored. The type of meter selected will depend on
•Minimum and Maximum Flow
•Turndown Ratio
•Type of gas equipment ( lab bench equipment, boiler load, catering equipment, laundry equipment, workshop equipment / furnace / kiln )
For low volumes of gas usage ( laboratory Bunsen Burners, Laundry Tumble Driers ) for accurate monitoring a positive displacement ( Diaphragm ) meter must be used.
To monitor the pulse output from any fiscal gas meter, a Chatter box or ATEX approved radio device has to be installed.
Approx £ 600 +Vat to install a chatterbox and pulse output cable.
•Pulse Output 1 will provide a connection for the gas supplier device to provide a monthly remote to import into their billing system.
•Pulse Output 2 is provided for daily monitoring of Interruptible gas supplies and large Firm Gas Supplies in excess of 250,000 BTU (Therms). 1000BTU = 0.3 kWh
•Pulse Output 3 is provide to connect the customers Energy Management System for live data usage display.
All this can be automated in an excel spreadsheet to speed up the calculation
CIBSE CPD
Now work out the permissible pressure loss for gas pipework. This is the limiting criteria for pipe sizing!
Use Equivalent Length method for fitting loss i.e.
+30% for fittings
(+30% for tracpipe < 32mm, +10% < 50mm)
1mbar / equivalent length of pipe
The selection of the correct type of gas meter and ancillary equipment is important otherwise some of the gas usage may not be monitored. The type of meter selected will depend on
•Minimum and Maximum Flow
•Turndown Ratio
•Type of gas equipment ( lab bench equipment, boiler load, catering equipment, laundry equipment, workshop equipment / furnace / kiln )
For low volumes of gas usage ( laboratory Bunsen Burners, Laundry Tumble Driers ) for accurate monitoring a positive displacement ( Diaphragm ) meter must be used.
An alternative for very low gas flows is the Delta QD Rotary Piston meter. They have been especially designed for industrial use and for secondary measurement and are particularly adapted when the flow can be low or irregular. ( Model QD25 1 to 25 m3 / hr and the QD60 2.5 to 60 m3 / hr )
For volume flows up to 160 m3/hr ( ~ 1750 kw /hr ) a diaphragm meter may used. However, this is a bulky meter and two to three times more expensive than an equivalent rotary meter. If the turndown ratio is not critical, especially if there is a space limitation, a rotary meter may be used. Example :- a gas supply a workshop with four 60 kw radiant heaters each controlled with an on / off thermostat then a rotary meter would be applicable.
The pressure drop across s the meter is also important, A 100mm pipe may be able to supply two boilers rated at 750 kw input, however the pressure drop across a 100mm meter located in the basement was sufficient to breach the Gas Safety Regulation for the boilers located five storeys above on the roof. Instead the 100mm was removed and an 80mm meter was installed adjacent to each boiler.
On the advice of Transco all sub gas meters should be installed with a chatter box, approved ATEX radio device or galvanic isolation device
For radio communications the university uses the best practise method adopted for the gas industry. A chatterbox will be installed to each sub meter ( Dresser 103-e ) interposed between the pulse output and the connection to the metering system using a non ATEX radio device or hard wire connection to a data logger.
Meters, solenoid valves and pipework all add a resistance to the system.
Meters should be selected to achieve optimum accuracy at minimum resistance
Pipe work (including bends and isolation valves) should be sized not to exceed 1mBar
Now work out the permissible pressure loss for gas pipework. This is the limiting criteria for pipe sizing!
available / equivalent length of pipe
Pressure losses
Available pressure = 21mBar
Gas boilers require 18mBar
therefore 3mbar pressure is spare!
(1mbar = 100 Pascal's = 0.01mh)
Exercise:
A small office block has a 50kW gas boiler & a ‘six hob’ gas cooker. Determine the total flow rate
Boiler output (kW) * 3600 / boiler efficiency / calorific value of gas = m3/h
Calorific value of gas (kJ/m3) = 37500,
British Standards
(The) Carriage of Dangerous Goods and Use of Transportable Pressure Equipment Regulations 2004. SI 2004 No 568. HMSO, 2004. http://www.opsi.gov.uk/si/si2004/20040568.htm
(The) Control of Substances Hazardous to Health Regulations 2002. SI 2002 No 2677. HMSO, 2002. http://www.opsi.gov.uk/si/si2002/20022677.htm
(The) Highly Flammable Liquids and Liquefied Petroleum Gases Regulations 1972. SI 1972 No 917. HMSO, 1972.
(The) Pressure Equipment Regulations 1999. SI 1999 No 2001. HMSO, 1999. http://www.opsi.gov.uk/si/si1999/19992001.htm
(The) Pressure Systems Safety Regulations 2000. SI 2000 No 128. HMSO, 2000. http://www.opsi.gov.uk/si/si2000/20000128.htm