Study Of 33/11 KV Substation And Power Distribution Under RG

No description
by

Gaurav Singh

on 18 August 2014

Comments (0)

Please log in to add your comment.

Report abuse

Transcript of Study Of 33/11 KV Substation And Power Distribution Under RG

About RGGVY Scheme :
Rajiv Gandhi Grameen Vidyutikaran Yojana scheme was launched for rural electrification.
It provides Free of cost service connection to all families Below Poverty Lines.
It promises a minimum daily power supply of 6- 8 hours.
It includes Creation of atleast one 33/11 kV (or 66/11 kV) sub-station in each block.
It provides Installation of at least one distribution transformer in each village / habitation.
REC is a nodal agency for this scheme.

Components Of 33/11 Kv Substation
1. Power Transformer :


Rated MVA (ONAN rating) :

5 MVA


No. of Phases :

3

Cooling medium :
Insulating Oil


Type of tap changer :

Off load tap Changer

Range of tappings :

+5% to –5% in steps of 2.5% each on
HV winding


Impedance (5 MVA) :

7.15%

Winding material :

Copper

Type of cooling :

ONAN

2. Substation Transformer :
4. Isolators :
3. Vaccum Circuit Breaker
Single Line Diagram Of 33/11 KV Substation
Study Of 33/11 KV Substation And Power Distribution Under RGGVY Scheme
GAURAV SINGH
11. AB (arial bundled) Cables :
10. Fuse
Pole Assembly For 33 Kv & 11Kv Lines
Distribution Pole Assembly
8. Cables and jointing kits :
6. Lightning Arrester :
HG (horn gap) Fuse
Hook Arrengement For Conductors
• Rated kVA (ONAN rating) :

100 kVA

• No. of Phases :

3
• Cooling medium :

Insulating Oil
• Impedance :

4.5%

• Type of cooling :

ONAN
• Type of tap changer :

Off load tap Changer
• Range of tapings :

+5% to -5% in steps of 2.5% each on HV winding

• Rated Normal Current :

630A for 11 kV
• Rated Normal Current :

1250A for 33kV
• Interrupting Capacity :

25kA for 3 sec
• Break Time :

<80ms
• Closing Time :

<150ms

DBCR type isolators are used in 33/11 kv substation
5. Instrument Transformers :
current transformer
potential transformer
Nominal Discharge current :
10kA

Housing :
Porcelain/Polymer
7. Meters :
tri-vector meter
Ammeter
Voltmeter
9. Stay set :
Stay wire
Stay Insulator
Turn Buckle
Anchor rod & plate
Guy Grip with thimble


Cut Out Fuse
LT Connectors
Street Light Fitting
Capacitor Bank Assembly On 2 Pole Structure
Auto Recloser Assembly
Automatic Voltage Booster On 11KV Line
Guying Arrangement
Turning Arrangement Of Conductors
REFERENCES :
BOQ Passed By PGCIL
REC Disc
PGCIL Library
33/11 Kv Substation Manual
google images
Full transcript