RCD's and similar protection

correct way to test RCd's

how not to test an RCD

Testing

RCDs should be tested with a RCD tester to ensure they operate within the specified time for the class type

If a manual test button is present, that should be tested as well. If on a portable device then every time it is used.

If an RCD does not operate properly then it shall be discarded

Names of RCD devices

3 Phase operation

Tripping Times

3 Phase RCD's operate by the same principal as single phase

But in this case an imbalance can be created by a phase to earth fault or a phase to phase fault.

The rcd will operate and open all phase and neutral conductors

RCD- residual current device

RCCB- residual current circuit breaker

GFCI- ground-fault current interrupter

(American version of an RCD)

ALCI- Appliance leakage current interrupter

(Canadian version of American GFCI)

RCBO- residual current circuit breaker with overload protection

CBELCB- core balanced earth leakage circuit breaker

Rcd's used for personal protection in NZ require their operation to verified as:

at rated residual current the device will operate within 300ms

at 5 times the rated current the device will operate within 40ms

at 1.4 times the rated current for pulsating DC the device will operate within 300ms

at 7 times the rated residual current for pulsating DC the device will operate within 40ms

Single Phase operation

Detects imbalances between phase and neutral

When there is a fault to earth, less current flows in the neutral

This creates a magnetic imbalance in the core, this is detected by the trip coil which opens the circuit